For the past two months, weve talked about cyanide tests, what
they mean and how they are performed. This time, our topic is
operating a typical cyanide destruct system, including some simple
techniques for improving its performance.
Cyanide oxidation is typically performed in two separate tanks,
each providing one "stage" of the destruction reaction.
The first stage utilizes sodium hypochlorite (or chlorine gas)
to convert cyanide to cyanate at elevated pH (10+). The cyanide
and chlorine react to form cyanogen chloride, which is then mixed
with more chlorine to form cyanate.
The first reaction between chlorine and cyanide-bearing wastes
is conversion of the simple cyanide in excess of that required
to solubilize the metallo-cyanide complexes. The reaction then
proceeds to form varying amounts of insoluble heavy metals containing
cyanide. The heavy metals actually trap some cyanide as they are
formed. Over time and with a large excess of chlorine, they may
further react with chlorine to form heavy metal hydroxides and
the reaction products from cyanide chlorination.
This last reaction proceeds very slowly. In fact, it is so slow
that complete destruction of all cyanide by chlorination at high
pH is not possible in a flow-through system. By lowering the pH
below 10, the ionization of cyanides increases and the activity
of the chlorine accelerates, resulting in more efficient cyanide
and cyanate destruction. In other words, at pH values above 10,
the cyanide/chlorine reaction almost completely stops at the cyanate
stage and usually leaves some residual of untreated cyanide. At
pH values lower than 10, the process favors conversion of cyanate
to carbon dioxide and nitrogen. Since these go off as gases, there
is more likelihood that the reaction will go to completion.
Cyanide wastes are additionally treated in a clarifier, where
insoluble metallo-cyanides are precipitated and removed in the
sludge.
Operating Details
The oxidation of cyanide in each chlorination tank is controlled
by an oxidation-reduction potential (ORP) meter. The meter reads
millivolt (mV) potential by means of a probe in the rinsewater
being treated. The mV reading is not critical and will vary from
one plant to the next, depending on the amount of oxidizable chemicals
in the rinsewater. The meter cannot distinguish between cyanide
and cuprous copper, for example.
The meter is functioning properly when it turns on the hypochlorite
pump when there is less than 10 ppm of chlorine in the oxidation
tank and shuts the pump off when 50 ppm is present. Whatever setpoint
(in mV) this condition corresponds to is the correct one. Operators
should not go by a given mV reading provided in the literature.
The easiest way to find this setpoint is to use potassium iodide/starch
test papers, which turn varying shades of blue if immersed in
rinse waters containing differing levels of chlorine. Some even
have a chart on the vial of papers that lets the technician estimate
what the chlorine concentration is. To set the ORP meter, the
operator dips a test paper in the liquid in the oxidation tank
and watches to see if it turns blue. If not, the hypochlorite
pump is turned on by adjusting the setpoint of the ORP meter and
the test is repeated every minute or so until a deep blue color
is obtained. At this point, the ORP meter is readjusted so that
it turns off the hypochlorite pump.
The paper should never test so strong in chlorine that the blue
color is washed out and only a blue stripe is present at the liquid/air
interface. Too much chlorine can cause severe problems in the
clarifier (floating sludge)! The next step is to see if the ORP
meter properly cycles around the setpoint. The pump should go
on just as the papers turn faint blue and within a few seconds
after they test white. The pump should go off when the papers
test deep blue, but before they test white with a blue stripe.
One note of caution on interpreting the test papers: If they are
dipped directly in the sodium hypochlorite, they will not turn
blue at all because the chlorine bleaches the paper instantly.
On a rare occasion, too much hypochlorite might be added to the
cyanide destruct tank by mistake (e.g., due to a broken probe
or stuck pump) . If the operator suspects that this is the case
(the scent of chlorine in the air usually is strong), some of
the waste should be diluted with water in a 5-gal bucket before
testing with the papers. If the papers turn blue, the sample is
way over-chlorinated. In such a case, the hypochlorite pump should
be left off until the first-stage cyanide destruct tank tests
a true "white." The clarifier may also have to be treated
for excess chlorine by adding sodium thiosulfate dissolved in
water (a few 50-lb bags should be kept handy).
Second Stage
Many waste-treatment operators assume that because everything
is "controlled" by meters that they dont have to monitor
the system very often. This is a big mistake. The operator should
check both chlorination compartments with test papers at least
twice a shift.
As stated earlier, the pH of the wastewater in the first stage
is not important as long as it is above 10. In the second stage,
however, a pH of 8 to 9 is required, so control is very important
here. At least twice-a-shift pH checks are essential in this compartment.
The reading of the pH meter/controller should not be trusted because
it can go awry when dirt or oil gets on the probe, leading to
drift under normal use. Also, pH is temperature sensitive, so
a calibration The setting that was okay last summer when the rinsewater
was 50 F will not be satisfactory in the winter when the water
is 35 F. (Some meters automatically compensate for temperature.)
The ORP meted In the second stage of the chlorination system should
be adjusted and sat so that the starch test papers yield a sky-blue
color and so that the waste entering the clarifier is either not
blue when tested or a very faint (almost impossible to see) blue.
The ORP and pH meter probes should be inspected once per shift
and cleaned, if necessary.
A rigorous program of probe maintenance must be implemented and
followed. The pH and ORP meters are only as good as the probes
they use to "senses the status of the system. A daily wipe
with alcohol to remove oil and grease from the probe is highly
beneficial. The operator should be sure that he wipes the right
part of the probe. The pH probe has a glass bulb that senses pH,
whereas the ORP probe has a metallic disc/strip. These need to
be cleaned. Should there be a stubborn film of metal hydroxide
on the probes, it can be removed by immersion in 10 to 20 percent
hydrochloric acid. A typical waste-treatment operator will check
all probes (and clean when necessary) at least twice per 8-hr
shift. Some check hourly.
Keeping spare probes on hand for each meter serves two purposes.
First, it keeps the system operating when a probe is damaged or
wears out. Second, it allows the operator to determine if a meter
is defective by changing to a probe he knows is sound.
High Cyanide
It is quite possible that even with a cyanide chlorination system
working at peak efficiency, the total cyanide in the discharge
will still be too high. This is because some cyanides are only
partially chlorinated or not chlorinated at all.
If cyanide plating is carried out on steel parts, the waste will
always have some iron cyanide in it. Worse yet, the iron cyanide
has a tendency to settle out in the clarifier, leading to cyanide
in the clarifier sludge. However, there are many different iron
cyanide compounds and some variations do not settle out in the
clarifier. These yield high-total-cyanide test results.
Experiments have shown that cyanide removal in the clarifier can
be improved by balancing the zinc and iron concentration in the
pH-adjust tank.
If there is a lot of zinc and a lot less iron, ferrous sulfate
can be added to the pH-adjust tank. The procedure is to dissolve
10 lb of ferrous sulfate to 55 gal of water and feed with a chemical
pump at 1 gal/hr. If there is a lot more iron than zinc in the
pH-adjust tank, zinc sulfate (at a similar feed rate) can be added
instead.
Recently, the above change was made for a zinc plater who had
a hard time meeting the limit of 1.9 mg/L total cyanide on a routine
basis. He meets the limit routinely now by adding ferrous sulfate
to his pH-adjust tank. Experimentation may be required with feed
rates and concentrations because every plant has a slightly different
waste.
Reference
1. K. Tanihara et al., Met. Fin., 85,131 (June 1987).